Function | Range | Resolution | Measuring range | Accuracy |
Earth resistance Auto range | 20¥Ø | 0.01¥Ø* | 0.00~20.99¥Ø | ¡¾1.5%¡¾0.05¥Ø |
200¥Ø | 0.1¥Ø | 16.0~99.9¥Ø | ¡¾2%¡¾0.5¥Ø |
100.0~209.9¥Ø | ¡¾3%¡¾2¥Ø |
1200¥Ø | 1¥Ø | 160~399¥Ø | ¡¾5%¡¾5¥Ø |
400~599¥Ø | ¡¾10%¡¾10¥Ø |
10¥Ø | 600~1260¥Ø | - |
AC current (50Hz / 60Hz) Auto range | 100mA | 0.1mA | 0.0~104.9mA | ¡¾2%¡¾0.7mA |
1000mA | 1mA | 80~1049mA | ¡¾2% |
10A | 0.01A | 0.80~10.49A |
30A | 0.1A | 8.0~31.5A |
Operating system | Earth resistance function : Constant voltage injection, Current detection, (Frequency : Approx.2400Hz) Dual Integration AC current function : Successive Approximation |
Over-range indication | "OL" is displayed when input exceeds the upper limit of a measuring range |
Response time | Approx.7 seconds (Earth resistance) Approx.2 seconds (AC current) |
Sample rate | Approx. 1 times per second |
Power source | DC6V : R6P(sizeAA manganese battery) ¡¿ 4pcs, or LR6(sizeAA alkaline battery) ¡¿ 4pcs |
Current consumption | Approx. 50mA (max. 100mA) |
Measurement time | Approx. 12 hours (when R6P is used) Approx. 24 hours (when LR6 is used) |
Auto power-off | Turns power off about 10 minutes after the last button operation. |
Applicable standards | IEC 61010-1 : 2001 (CAT.IV 300V Pollution degree2) |
Withstand voltage | AC5320Vrms / 5 seconds Between the Transformer jaws fitted parts and Case enclosure (except for jaws) |
Conductor size | Approx. 32mm max. |
Dimension | 246(L) ¡¿ 120(W) ¡¿ 54(D)mm |
Weight | Approx. 780g (including batteries) |
Accessories | Battery R6P : 4pcs Instruction manual : 1pc 8304 (Resister for operation check : 1pc) 9128 (Hard case : 1pc) |